_目rh骊l-:八= L 发电设计 中压电缆系统接地电容电流计算方法 删姗 中压电缆系统 接地电容电流计算方法 陈景涛 (上海艾能电力工程有限公司,上海200023) 摘要:本文提供了单芯电缆、分相铅(铝)护套电缆、屏蔽型电缆每相对地电容的估算方法,通过算例分析对 比了中压电缆系统接地电容电流常用估算方法的计算结果。认为由于电缆材料和结构的变化,在具体工程中 不宜再利用《电气设计手册》估算公式来计算中压电缆系统的接地电容电流值,而应根据厂家提供的电缆每 相对地电容值利用理论公式计算。 关键词:电缆每相电容;中压不接地系统;单相接地电流。 中图分类号:TM621文献标志码:B文章编号:1671・9913(2015)02-0041—03 Calculation Method of Grounding Capacitive Current for MV Cable System CHEN Jing-tao (Shanghai Intelligence Power Electric Engineering Co.,Ltd.,Shanghai 200023,China) Abstract:This paper briefly described assessment method for phase—to—ground capacitive current of metal armor cable, simply analyzed and compared the calculation result via sample MV cable grounding capacitive current.Figured out that assessment formula of MV cable grounding capacitive current in Electrical Design Manual is no longer practicality in detailed project,because of different cable material and structure,which should be calculated theoretically,based on cable phase・-to・-rgound capacitive parameter provided by cable producer. Key words:cable phase-to—ground capacitor;MV non-grounded system;single phase grounding current. 1概述 为由于电缆材料和结构的变化,在具体工程设 电力工程设计中,常常为中压电缆系统的 计中不宜再利用《设计手册》估算公式来计算 单相接地电容电流值而感到纠结。有的根据电 中压电缆系统的接地电容电流值,而应根据厂 家提供的电缆每相对地电容值利用理论公式 缆厂家提供的每相对地电容值利用理论公式计 计算。 算,有的根据电压等级、电缆长度、电缆截面 按《设计手册》的估算公式计算,而其计算结 2中性点不接地系统的单相接地电流计算 果相差往往比较大。本文提供了单芯电缆、分 2.1理论计算公式 相铅(铝)护套电缆、屏蔽型电缆每相对地电容 中性点不接地系统的等值电路和相量图见 的估算方法;通过算例分析对比了中压电缆系 图1。在正常运行时,回路各相对地电压 、 统接地电容电流常用估算方法的计算结果。认 、 是对称的,其大小为相电压。如线路经 收稿日期:2014—07—09 作者简介:陈景涛(1981.),男,上海崇明人,工程师,主要从事发电厂电气系统的设计与研究。 2015年04月第2期 .41